Open-mesh epoxy prepreg netting, Class F/H, for coil reinforcement
Fiberglass mesh braided into a reticulation structure from fiberglass yarn and coated with epoxy resin, then baked. Used as reinforcement insulation in cast-resin dry-type transformers and reactors.
- Temperature class
- Class F/H
- Thickness
- 0.5–2.4 mm
- Resin content
- 12–18%
- Width
- ≤1000 mm
Technical data
| Property | Unit | Value |
|---|---|---|
| Material | — | Fiberglass netting + epoxy resin |
| Normal thickness | mm | 0.5 / 0.6 / 0.8 / 1.0 / 1.2 / 1.6 / 2.0 / 2.2 / 2.4 |
| Normal length | mm | 100 / 50 / 40 |
| Width | mm | 0.2–1.2 m band / ≤1000 |
| Resin content | % | 12–18 |
| Tensile strength | N/mm | 800 / 1000 / 1500 / 2400 / 3400 / 4200 / 4800 / 5300 |
| Mesh size (warp × weft) | mm | 5 × 4 / 6 × 5 / 10 × 7 |
| Weight | g/m² | 180 / 230 / 360 / 620 / 680 / 760 / 800 / 880 |
| Breakdown voltage | kV | ≥18 |
| Insulation resistance | Ω | ≥1×10¹³ |
| Compression strength | MPa | ≥20 |
| Bending strength | MPa | ≥80 |
| Strength of interpose electric | kV/mm | ≥9 |
| Temperature class | — | Class F / H |
Values are typical values or ranges from our product data. Bulk supply is subject to the approved specification, sample and test report. If a parameter you need is not listed here, ask our engineers for the full test report for that grade.
Key features
- Open mesh aids resin penetration and improves coil crack resistance.
- Prepreg epoxy cures into an integrated structure with the coil.
- Supplied in rolls with slitting and custom widths.
Applications
Coil reinforcement insulation in cast-resin dry-type transformers and reactors; HV insulation structures.
Why it fits
Open mesh lets the casting resin through while the cured netting holds the coil together and resists cracking.
Ordering information
To receive a quotation, please confirm:
- Product and grade
- Thickness and width (and roll or sheet size)
- Temperature class
- Quantity and delivery form (roll / sheet / die-cut / machined)
- Destination port and required delivery date
For machined parts, attach a drawing in PDF, DWG or STEP format. Datasheets, COAs and batch test data are available on request.